Transformer Calculator – Turns Ratio & Secondary Voltage
Use this free Transformer Calculator to find the output (secondary) voltage of a transformer from the input voltage and the number of turns on each coil, using Vs/Vp = Ns/Np.
A transformer is two coils of wire sharing one iron core, touching nothing, exchanging everything. Alternating current in the first (primary) coil builds a magnetic field that rises, falls and reverses fifty or sixty times a second; the iron core gathers that changing field and threads it through the second (secondary) coil, where — by Faraday's law of induction — it generates a voltage. No moving parts, no electrical contact between input and output: just a magnetic conversation between windings, and the ratio of their turns decides the ratio of the voltages.
That ratio is the whole secret, and it cuts both ways. More turns on the secondary than the primary and the voltage steps up; fewer and it steps down. But energy keeps the accounts honest: in an ideal transformer the power out equals the power in, so a voltage stepped down tenfold comes with a current stepped up tenfold, and vice versa. A transformer trades voltage against current at an exchange rate set by its turns — it never manufactures power, which is why the device is best pictured not as an amplifier but as a gearbox for electricity.
It is difficult to exaggerate what this device made possible. Because transformers exist, electricity can be generated at moderate voltage, stepped up to hundreds of thousands of volts for a cross-country journey at tiny current (and tiny losses), then stepped down in stages to the safe voltage of a wall socket. The entire AC grid is a cascade of transformers; so, in miniature, is every phone charger, doorbell and welder. This calculator finds the secondary voltage from the turns ratio, classifies the transformer as step-up, step-down or isolation, and — if you supply the primary current — works out the secondary current for the ideal case.
Formula
Vs ÷ Vp = Ns ÷ Np → Vs = Vp × (Ns / Np) • for an ideal transformer, Is = Ip × (Np / Ns)
The turns ratio is the transformer's identity card. Voltage follows it directly — Vs is Vp scaled by Ns/Np — and current follows it inversely, because the ideal transformer's power balance (Vs × Is = Vp × Ip) leaves no other possibility. Rearranged, the same relation finds a missing turn count from a target voltage, as in Example 6. Two honest caveats: the formulas describe the ideal, lossless transformer, and real devices surrender a few percent to heat (large grid units exceed 98% efficiency; small plug-top units may manage only 70–85%); and the voltages are the values under rated conditions — a small transformer's unloaded output often sits noticeably above its label. Turns themselves are pure counts, so the ratio is exact even when the hardware is not.
| Symbol | Meaning | Units |
|---|---|---|
| Vp, Vs | primary (input) and secondary (output) voltages | volts (V) |
| Np, Ns | turns of wire on the primary and secondary coils | pure counts |
| Ip, Is | primary and secondary currents (ideal case) | amps (A) |
| Ns/Np | turns ratio — above 1 steps up, below 1 steps down | no units |
Volts per turn: the shared heartbeat of the two coils
Why should voltage follow turns so exactly? Because induction pays by the turn. The core carries one magnetic flux, rising and falling as a single quantity, and every loop of wire wrapped around that core — primary or secondary — has the same changing flux threaded through it, so every loop gains the same induced voltage. If the flux's rhythm grants, say, 0.2 volts per turn, then a primary of 1,200 turns presents 240 V and a secondary of 120 turns presents 24 V: the voltages stand exactly as the turn counts stand, because both coils are paid the same rate for different amounts of identical labour.
This also explains the primary's quiet self-regulation, the subtlest part of the machine. The primary is connected to a fixed supply; the voltage induced in it by the core's flux (its back-EMF) must nearly match that supply. Load the secondary and its current creates flux opposing the core's, the back-EMF dips, and the primary automatically draws more current from the supply until balance is restored. The transformer thus orders exactly the power the load demands, through a magnetic feedback loop with no electronics in sight — and idles, nearly, when the secondary is disconnected, which is why an unloaded transformer draws only a whisper of current.
How to use
- Enter the primary (input) voltage and the number of turns on the primary coil.
- Enter the number of turns on the secondary coil.
- Click "Calculate" to get the secondary (output) voltage and the turns ratio. If you also enter the primary current, you will get the secondary current for an ideal (100% efficient) transformer.
- Read the classification: ratio below 1 is step-down, above 1 is step-up, and exactly 1 is an isolation transformer — same voltage, but with the output electrically separated from the mains for safety.
Worked examples
Example 1 — a step-down transformer. A transformer has a primary voltage of 240 V, with 1200 turns on the primary coil and 120 turns on the secondary coil.
Vs = Vp × Ns ÷ Np = 240 × 120 ÷ 1200 = 24 V.
The turns ratio is 120 : 1200 = 1 : 10, so this is a step-down transformer — the kind that feeds doorbells, model railways and low-voltage lighting.
Example 2 — stepping up. A primary of 100 turns is fed with 12 V; the secondary has 1,000 turns.
Vs = 12 × 1000 ÷ 100 = 120 V. Ten times the turns, ten times the voltage — and, by the power balance, a tenth of the current available at the output. Step-up transformers start the electricity grid's long journeys and fire camera flashes and neon signs at the small end of life.
Example 3 — the current trade. Example 1's transformer draws a primary current of 0.5 A. What secondary current can it supply?
Is = Ip × Np ÷ Ns = 0.5 × 1200 ÷ 120 = 5 A. Check the power: in, 240 × 0.5 = 120 W; out, 24 × 5 = 120 W. The voltage fell tenfold, the current rose tenfold, and the power — the thing that does the work — passed through unchanged.
Example 4 — the grid's great step-up. A power station generates at 25 kV; the transmission lines run at 400 kV.
The ratio is 400 ÷ 25 = 16, so a primary of 500 turns needs a secondary of 500 × 16 = 8,000 turns. For 100 MW of power, the current falls from 100,000,000 ÷ 25,000 = 4,000 A at generator voltage to 100,000,000 ÷ 400,000 = 250 A on the lines — and since cable losses follow I², they shrink by a factor of 16² = 256. That single factor is the economic foundation of the entire grid.
Example 5 — a phone charger. A charger turns 240 V mains into 5 V for a phone.
The ratio is 240 ÷ 5 = 48 : 1; if its secondary has 24 turns, the primary has 24 × 48 = 1,152 turns. (Real chargers cheat elegantly — they first chop the supply into high-frequency AC so the transformer can be tiny — but the turns arithmetic is exactly this.)
Example 6 — designing for a target voltage. You need 12 V from a 120 V supply, and a primary coil of 600 turns is on the shelf. How many secondary turns?
Ns = Np × Vs ÷ Vp = 600 × 12 ÷ 120 = 60 turns. The formula run in its design direction: name the voltages, and the winding is specified.
Transformers in real life
The electricity grid. A kilowatt-hour's journey may pass through half a dozen transformers: stepped up at the power station to 400 kV, down at regional substations through 132 kV and 33 kV, down again to 11 kV for industry, and finally down at the pole or green cabinet on your street to the 230 V of your sockets. Each hop is Example 4's arithmetic in different dress.
Chargers and adapters. Every wall-wart is a transformer (or its high-frequency descendant) trading mains voltage down to the gentle volts electronics drink — with the current trade running in the charger's favour, since a modest mains current becomes a healthy charging current at 5 V.
Doorbells and shaver sockets. The doorbell transformer's humble 24 V (Example 1) can be wired by anyone without danger, and the shaver socket in a bathroom contains an isolation transformer — ratio 1:1, changing nothing but separating the output from earth-referenced mains, so a fault has no path through a wet user.
Arc welding. A welder is a step-down transformer taken to extremes: mains voltage becomes a few tens of volts while the current climbs into hundreds of amps — Example 3's trade pushed until the secondary current can melt steel. The thick secondary winding, sometimes just a few turns of bar, is the turns ratio made visible.
Induction cooking. An induction hob is a transformer whose secondary is the pan itself: the coil under the glass is a primary, the pan's base a single-turn secondary, and the current induced in it — enormous, because the "turns ratio" is so lopsided — heats the pan directly while the glass stays cool.
Audio and microphones. Small transformers match impedances between microphones, amplifiers and loudspeakers, trading voltage and current so that maximum power transfers — the same ratio arithmetic, tuned for signals a million times weaker than a doorbell's.
Why the grid speaks high voltage: the I² argument
Example 4 deserves its own spotlight, because it justifies the largest machines on Earth. Power delivered is V × I, so for a fixed power, raising the voltage lowers the current in proportion. But the loss in the lines is I²R — it follows the square of the current. Step the voltage up 16 times and the current falls 16-fold while the losses fall 256-fold. Run the numbers the other way and the alternative collapses: sending 100 MW at 25 kV means 4,000 A, needing absurd copper and still bleeding megawatts as heat. There was a famous nineteenth-century contest over exactly this — Edison's DC, which could not be transformed, against the AC system of Tesla and Westinghouse, which could. The transformer's existence settled it: the modern world is AC because the turns ratio made distance cheap.
Quick reference: transformers you already own
| Application | Input | Output | Type |
|---|---|---|---|
| phone charger | 240 V | 5 V | step-down |
| doorbell | 240 V | 24 V | step-down |
| bathroom shaver socket | 230 V | 230 V | isolation (1:1) |
| microwave oven (magnetron supply) | 240 V | about 2,000 V | step-up |
| arc welder | 240 V | about 25 V at hundreds of amps | step-down |
| grid transmission | 25,000 V | 400,000 V | step-up |
| street pole transformer | 11,000 V | 230 V | step-down |
One table, one rule: find the turns ratio hiding inside each row — 48:1 in the charger, 1:16 at the power station — and you have understood every transformer you will ever meet.
The one-coil cousin: the autotransformer
Not every transformer keeps its coils separate. An autotransformer uses a single winding with a tap part-way along it: the whole winding serves as the primary, the tapped portion as the secondary, and the same turns-ratio law governs the voltages. Sharing copper makes it cheaper, smaller and slightly more efficient than the two-coil design — the variable bench supply (a Variac) is an autotransformer whose tap slides. The sacrifice is isolation: input and output remain electrically connected, so the safety break of the two-coil design is lost, and autotransformers are never used where that separation is the point. The calculator's formulas apply unchanged; only the construction differs.
Common mistakes
- Feeding a transformer DC and expecting output. Steady DC makes a steady field, and steady fields induce nothing after the first instant — the primary becomes merely a low resistance across the supply and overheats. Transformers are AC machines; DC must be chopped into pulses first, as switch-mode supplies do.
- Inverting the turns ratio. Vs = Vp × Ns/Np — secondary over primary. Swapping them turns a 24 V doorbell supply into a (theoretical) 2,400 V surprise on paper; check the direction by asking whether the answer should step up or down.
- Expecting free power. Stepping voltage down multiplies the available current, never the power. A 24 V, 5 A secondary is a 120 W device however it is read; demanding 240 W from it overloads the primary side and the core alike.
- Trusting the label voltage off-load. Small transformers are rated at full load; disconnected, their output can sit 10–20% high, because the winding resistances stop dropping voltage. Measuring 27 V from a "24 V" unit with no load is normal, not a fault.
- Ignoring efficiency and frequency. Real transformers lose a few percent as heat in the core and windings, and they are designed for a rated frequency — a 60 Hz unit run on 50 Hz draws more magnetising current and may run hot. The calculator's ideal answers are the target the hardware approaches.
FAQ
Why does a transformer only work with AC?
A transformer works by electromagnetic induction: the changing magnetic field from the primary coil induces a voltage in the secondary coil. AC keeps the field changing; steady DC produces a constant field, so after the first moment nothing is induced.
What is the difference between step-up and step-down?
If the secondary coil has more turns than the primary (Ns > Np), the voltage steps up. If it has fewer turns, the voltage steps down — like the example above, which turns 240 V mains into a safer 24 V.
Does a transformer create extra power?
No. In an ideal transformer the power out equals the power in (Vs × Is = Vp × Ip), so stepping the voltage down steps the current up, and vice versa. Real transformers lose a little energy as heat, so they are not quite 100% efficient.
What is the turns ratio?
Simply Ns ÷ Np — the secondary turns divided by the primary turns. It is the single number that fixes the voltage ratio, and the inverse of the current ratio. A ratio of 1:10 (0.1) steps voltage down tenfold.
Why is the iron core made of thin laminated sheets?
To fight eddy currents. The changing flux would otherwise induce swirling currents inside a solid core, wasting energy as heat. Laminations — insulated sheets stacked together — break the swirls' paths while letting the magnetic flux pass along the sheets.
How efficient are real transformers?
Remarkably. Large grid transformers exceed 98–99% efficiency, among the most efficient machines ever built; small plug-top units manage perhaps 70–85%, losing the rest as the warmth you feel. The losses split between the core (hysteresis and eddy currents) and the windings (I²R).
Why are phone-charger transformers so tiny?
Frequency. A core can handle more power per cycle at higher frequency, so chopping the supply to tens of thousands of hertz lets a thimble-sized transformer do a 50 Hz brick's job. The turns-ratio law is unchanged — switch-mode chargers are this page with a faster heartbeat.
What is an isolation transformer for?
Safety through separation. With a 1:1 ratio the voltage is unchanged, but the output has no connection to the mains or earth, so touching one output wire cannot complete a circuit through your body to ground. Hospital equipment, shaver sockets and repair benches use them for exactly that break in the chain.
Why do transformers hum?
The core's laminations physically flex as the magnetic field alternates — an effect called magnetostriction — at twice the mains frequency, and loose laminations rattle sympathetically. The hum is the sound of the field breathing; it grows with load and age.
Can a step-down transformer be run backwards as a step-up?
Electrically, yes — feed the secondary and the primary becomes the output, with the ratio inverted. In practice, insulation ratings and winding resistances were designed for the original direction, so it is done cautiously and at reduced power, but the physics is perfectly symmetrical.