AC Power Calculator – Real, Apparent & Reactive Power (P, S, Q)
Use this free AC Power Calculator to split an AC load into real power P, apparent power S and reactive power Q. Enter the RMS voltage, RMS current and the phase angle between them — only the part of the current in step with the voltage does useful work.
The complication is that in AC, voltage and current need not rise and fall together. Feed a pure resistor and they march in step: every instant's product of volts and amps is positive, energy flows one way, and the average power is simply V × I. Feed an inductor or a capacitor and the current slides out of step — up to a quarter-cycle late or early — so that during part of each cycle the product goes negative and energy flows back to the supply. The load still draws current, the cables still carry it and heat up, but only a fraction of the apparent power does lasting work. Untangling that fraction from the rest is the whole job of this page.
The untangling produces three quantities with three different units, and keeping them straight is most of AC power engineering. Apparent power S, in volt-amperes, is the raw product V × I — what the supply must be built to deliver. Real power P, in watts, is the part converted irreversibly into work, heat and light — what the meter bills for. Reactive power Q, in vars, is the part that sloshes into magnetic and electric fields and back, twice per cycle, accomplishing nothing on average yet demanding current-carrying capacity all the while. The three form a right-angled triangle, S² = P² + Q², whose angle is the phase angle φ and whose cosine is the power factor.
This calculator performs the split from the three numbers a measurement usually gives you: the RMS voltage, the RMS current, and the phase angle between them (positive when the current lags, as in motors and other inductive loads; negative when it leads, as with capacitors). It returns S, P, Q and the power factor — the four numbers that decide cable sizes, transformer ratings, electricity tariffs and capacitor banks.
Formula
P = Vrms × Irms × cos φ • S = Vrms × Irms • Q = Vrms × Irms × sin φ • power factor = cos φ
The triangle rearranges freely: Q = √(S² − P²) if you know the other two sides, P = √(S² − Q²), and φ = cos−1(P/S) = tan−1(Q/P). If you know the load's impedance instead of the angle, cos φ = R/Z recovers the same triangle from the impedance side. Two disciplines matter. First, V and I must both be RMS values — peak values inflate S by a factor of two. Second, the sign of φ (and hence of Q) carries meaning: positive for inductive loads whose current lags, negative for capacitive loads whose current leads. Drop the sign and you lose the information that tells you whether a correction capacitor will help or harm.
| Symbol | Meaning | Units |
|---|---|---|
| P | real (active) power — converted to work, heat, light | watts (W) |
| S | apparent power — total the supply must deliver, S = V × I | volt-amperes (VA) |
| Q | reactive power — exchanged with fields, does no net work | vars (var) |
| φ | phase angle between voltage and current | degrees (°) |
| pf | power factor, pf = cos φ = P/S | dimensionless, 0 to 1 |
| Vrms, Irms | RMS voltage and current | volts (V), amps (A) |
Where the three powers come from: one cycle under the microscope
Multiply the instantaneous voltage by the instantaneous current and plot the product through one cycle; the three powers fall out of that single curve. With φ = 30°, the product curve still rises and falls twice per cycle, but it now dips below zero for a slice of each half-cycle — those negative dips are the returned energy, the visible signature of Q. The curve's average height is P. Its peak-to-average geometry encodes S. Nothing about the split is bookkeeping convention: the negative dips are real current, flowing backwards through real cables, heating them exactly as forward current does.
That is the deep reason utilities care. A load drawing 5 A at a power factor of 0.5 loads the network like a 5 A load — cables, transformers and generators must all be sized for the full apparent power — while delivering only half the watts a 5 A resistive load would. The missing watts are not lost; they were never converted. But the infrastructure cost is identical, so tariffs for large users price the triangle, not just the watts: many contracts penalise a power factor below 0.9 or 0.95, and the standard remedy is a bank of capacitors whose negative Q cancels the motors' positive Q locally, before it reaches the meter.
Notice, too, what Q is for. The reactive sloshing is not waste in the sense of a defect: a motor cannot turn without its magnetic field, and that field must be built and collapsed every half-cycle — Q is the power that does the building. The inefficiency is only in transporting that energy back and forth over long distances. Generate Q at the load, with a capacitor on site, and the motor keeps its field while the supply network sees a nearly pure P. Power-factor correction is logistics, not magic.
How to use
- Enter the RMS voltage and RMS current of the load — nameplate values are RMS already; if you measured a peak on a scope, divide by √2 first.
- Enter the phase angle φ between voltage and current in degrees (0° for a pure resistor, positive for an inductive load, negative for a capacitive one).
- Click "Calculate" for the real power P, apparent power S, reactive power Q and the power factor.
- Read Q's sign as the diagnosis: positive Q asks for capacitors to correct it; negative Q means the load is already capacitive and capacitors would make things worse.
Worked examples
Example 1 — a single-phase motor. A motor runs on 230 V RMS, draws 5 A RMS, with the current lagging by φ = 30°.
S = 230 × 5 = 1150 VA.
P = 1150 × cos 30° = 1150 × 0.866 = 995.93 W — this is the power that does work and appears on the bill.
Q = 1150 × sin 30° = 575 var, and the power factor is cos 30° = 0.87.
Example 2 — a pure resistive heater. A heater on 230 V draws 10 A with φ = 0°. S = 230 × 10 = 2300 VA; P = 2300 × cos 0° = 2300 W; Q = 2300 × sin 0° = 0 var; pf = 1. With no phase shift the triangle collapses to a line: everything delivered is converted, which is why heaters and incandescent lamps never attract power-factor penalties.
Example 3 — a three-phase-style industrial load (per-phase figures). A large machine draws 20 A at 400 V with φ = 45°. S = 400 × 20 = 8000 VA; P = 8000 × cos 45° = 5656.85 W; Q = 8000 × sin 45° = 5656.85 var; pf = 0.71. Half the delivered volt-amperes are pure field-sloshing — a load like this, uncorrected, is exactly what utility penalty clauses are written about.
Example 4 — a capacitive load. A bank of LED drivers and correction capacitors draws 2 A at 230 V with the current leading by 60°, so φ = −60°. S = 460 VA; P = 460 × cos(−60°) = 230 W; Q = 460 × sin(−60°) = −398.37 var; pf = 0.5. The negative Q is not an error — it is this load's gift to the network, available to cancel positive Q from motors elsewhere on the same bus.
Example 5 — correcting a factory's power factor. A plant consumes P = 100 kW at pf = 0.7. Its apparent power is S = 100,000 / 0.7 = 142,857.14 VA and its reactive power Q = √(S² − P²) = 102,020.41 var. To correct to pf = 0.95, the allowed Q falls to P × tan(cos−1 0.95) = 32,868.41 var. The capacitor bank must therefore supply 102,020.41 − 32,868.41 ≈ 69.15 kvar of negative Q — after which the supply delivers only 105,263.16 VA for the same 100 kW of work, and the plant's current falls by more than a quarter.
Example 6 — a well-behaved household load. A modern appliance draws 13 A at 230 V with φ = 20°. S = 2990 VA; P = 2990 × cos 20° = 2809.68 W; Q = 2990 × sin 20° = 1022.64 var; pf = 0.94. Domestic meters bill only the 2.81 kW, but the house wiring and the street transformer must still carry the full 13 A — the triangle quietly at work behind a plug.
AC power in real life
Electricity billing. Homes are billed for P (kWh), but large industrial users are billed or penalised on the whole triangle — maximum demand in kVA and power-factor surcharges both come straight from S and cos φ.
Generator and UPS sizing. Generators and UPS units are rated in VA (or kVA) because their windings and inverters feel S, not P. A 1000 VA UPS cannot run a 1000 W load at pf 0.7 — it can run 700 W of it. The watt rating and VA rating on the box are this triangle printed twice.
Power-factor correction capacitors. The capacitor bank in Example 5 is standard industrial furniture: switched banks of capacitors that track the load and hold the plant's pf near 0.95–0.99, paying for themselves in avoided penalties and freed transformer capacity.
Motor nameplates. A motor's plate quotes current at full load — the S-side current. Two motors with identical shaft power can draw quite different currents if their power factors differ, which is why electricians size cables from the plate current, never from the kilowatts.
Renewables and inverters. Modern grid codes require solar inverters and wind converters to supply or absorb Q on command ("volt-var" control), turning them into distributed correction devices that hold up network voltage — reactive power as a grid service, bought and sold.
Welding sets and lifts. Welders and older lift motors run at notoriously low power factors (0.5–0.7) with heavy current draw. Their supplies, breakers and cables are all specified from S — a welder "rated 200 A" is a statement about the triangle, not the arc's watts.
Quick reference: one 1000 VA supply at six power factors
| Power factor | φ | P from 1000 VA | Q from 1000 VA |
|---|---|---|---|
| 1.00 | 0° | 1000 W | 0 var |
| 0.95 | 18.19° | 950 W | 312.25 var |
| 0.90 | 25.84° | 900 W | 435.89 var |
| 0.80 | 36.87° | 800 W | 600 var |
| 0.70 | 45.57° | 700 W | 714.14 var |
| 0.50 | 60° | 500 W | 866.03 var |
The table's lesson is asymmetry: between pf 1.0 and 0.9 the watts barely notice, but below 0.8 the reactive share explodes — at pf 0.5 the load exchanges more reactive power (866 var) than real power (500 W). This is why correction efforts target the worst offenders first, and why a modest capacitor bank produces outsized relief on a heavily inductive network.
Three-phase power: the same triangle, three times over
Industrial power arrives as three phases, but the triangle survives intact — it simply applies to the totals. For a balanced three-phase load, S = √3 × Vline × Iline, and P = √3 × Vline × Iline × cos φ, with the same φ and the same pf. Everything this page says about correction, billing and sizing applies unchanged; only the √3 bookkeeping for line quantities is new. When a problem gives you per-phase values, run this calculator per phase and multiply P, Q and S by three — the power factor, being a ratio, stays exactly where it was.
A practical consequence follows for anyone planning corrections or new equipment: audit before you buy. A power-quality survey that separates displacement from distortion, and logs all three powers over a full working week rather than a single visit, costs far less than a capacitor bank sized from a nameplate guess — and its data feeds straight into the three modes of this calculator, turning a month of meter readings into an exact kvar figure, a defensible cable size and a tariff forecast the finance department can check.
Common mistakes
- Using peak instead of RMS values. S = V × I assumes both are RMS. Feeding in peak values (325 V for a 230 V supply) inflates every power by a factor of two and produces a fictional triangle.
- Adding P and Q to get S. The sides combine by Pythagoras: S = √(P² + Q²). For Example 1, 995.93 + 575 = 1570.93 is wrong; S is 1150 VA.
- Dropping the sign of φ. +30° (inductive) and −30° (capacitive) give the same P but opposite Q. Correction decisions live entirely in that sign — lose it and you may add capacitors to a load that needed inductors.
- Confusing kW with kVA when sizing equipment. A generator, UPS or transformer is limited by S. Quoting a load's watts to size them understates the requirement by the power factor — at pf 0.7, by over 40%.
- Assuming reactive power is "wasted" energy that shows on the bill. Domestic kWh meters register only P. Q's cost is indirect — bigger currents, hotter cables, demand charges and penalties — which is why correction is an infrastructure decision, not an energy-saving one.
FAQ
What is the difference between P, S and Q?
S (volt-amperes) is the total power the supply must deliver. P (watts) is the useful part converted to work, heat or light. Q (vars) is the part that sloshes back and forth into magnetic and electric fields each cycle without doing net work.
Why do electricity companies care about power factor?
A low power factor means more current for the same useful watts, which heats cables and loads transformers. Industrial users are often charged extra unless they correct the power factor, usually with capacitors.
Can reactive power be negative?
Yes. By convention Q is positive for inductive loads (motors, coils) and negative for capacitive loads. That sign is exactly why adding capacitors can cancel a motor's reactive power.
What power factor do utilities consider acceptable?
Most require large users to stay at or above 0.9, many at 0.95, measured at the meter. Below the threshold, tariffs add a reactive-energy or demand surcharge. Homes are usually exempt — the triangle is enforced where it is big enough to matter.
Is power factor the same as efficiency?
No. Efficiency compares useful output with real power input (Pout/Pin); power factor compares real power with apparent power (P/S). A motor can be 90% efficient and still run at pf 0.8 — the two ratios describe different losses and different triangles.
How do I measure φ without an oscilloscope?
A power-quality meter or clamp meter with a pf readout computes it directly. Alternatively, measure P with a wattmeter and V and I with ordinary meters: pf = P/(V × I), and φ = cos−1(pf). The sign — leading or lagging — needs the scope or a meter that reports it.
Can power factor exceed 1?
No. Since P ≤ S always (the hypotenuse is the longest side), pf = P/S ≤ 1. A reading above 1 signals distorted waveforms being measured with sine-wave assumptions, or a wiring error — not a miraculous load.
Why is Q measured in vars instead of watts?
To keep the books honest. The var (volt-ampere reactive) flags a quantity that has the dimensions of power but performs no net work, so it is never confused with billable watts on a nameplate, a tariff sheet or a triangle.
Do capacitors "consume" negative reactive power?
They supply it, in the accounting sense: a capacitor's Q is opposite in sign to an inductor's, so connecting the two lets their reactive exchanges happen locally between themselves instead of travelling to the generator. Nothing is consumed; the sloshing is just given a shorter path.
What happens at φ = 90°?
P = 0: a pure inductor or capacitor draws current and apparent power but converts nothing on average. Real loads never sit exactly there, but lightly loaded motors drift towards it, which is why an idling motor has a dreadful power factor despite drawing modest current.